1
00:00:00,080 --> 00:00:06,056
When you live in a cold place like I do, these&nbsp;
whole home humidifiers are great.

2
00:00:06,056 --> 00:00:11,080
Which is why it's such a shame that they're also so terrible.

3
00:00:11,080 --> 00:00:12,874
What do I mean by that?

4
00:00:12,874 --> 00:00:17,006
Well, if you've got one of these or you are looking into getting one,

5
00:00:17,006 --> 00:00:22,052
you&nbsp;should be aware that they need much more attention from you than you might expect.

6
00:00:22,052 --> 00:00:29,385
Not only can these&nbsp;rather easily fail in such a way that can cause catastrophic damage to your home's heating system,

7
00:00:29,385 --> 00:00:36,159
but they can also cause significant damage to your home itself if you simply let them run unattended.

8
00:00:36,159 --> 00:00:38,376
See, the thing that makes them great -

9
00:00:38,376 --> 00:00:43,994
the ability to add lots of moisture to the air 
very quickly&nbsp;without you having to do anything

10
00:00:43,994 --> 00:00:49,199
- also makes them a problem 
when the temperature outside gets very&nbsp;cold.

11
00:00:49,199 --> 00:00:56,264
But today, I am going to fix that problem 
by giving it just a little more smarts than it had&nbsp;before.

12
00:00:56,264 --> 00:00:58,487
First though, a little backstory.

13
00:00:58,487 --> 00:01:02,805
In 2021, I made a video on freestanding humidifiers,

14
00:01:02,805 --> 00:01:08,754
and&nbsp;the comments were filled with folks wondering why I didn't talk about centrally ducted humidifiers&nbsp;like this one

15
00:01:08,754 --> 00:01:11,119
beyond a basic mention.

16
00:01:11,119 --> 00:01:16,604
Well, partly that's because back then I was living in&nbsp;a different home and I didn't have one of these.

17
00:01:16,604 --> 00:01:21,061
But the bigger reason was that if you want to add&nbsp;a humidifier,

18
00:01:21,061 --> 00:01:27,992
it's a lot easier and cheaper to buy one that you 
just plop somewhere and fill with&nbsp;water.

19
00:01:27,992 --> 00:01:32,744
Many of them are large enough 
to work just fine as a whole-home humidifier.

20
00:01:32,744 --> 00:01:37,004
Plus, freestanding&nbsp;units don't care 
what kind of heating system you have.

21
00:01:37,004 --> 00:01:41,884
So, if your home is heated with radiators&nbsp;
or some other kind of ductless heating system,

22
00:01:41,884 --> 00:01:43,574
like certain kinds of heat pump,

23
00:01:43,574 --> 00:01:45,530
those will work&nbsp;fine.

24
00:01:45,530 --> 00:01:51,092
The humidifier I'm talking about today 
requires both a centrally ducted heating system

25
00:01:51,092 --> 00:01:54,125
and a plumbed connection to a water line.

26
00:01:54,125 --> 00:01:57,850
So, it's not universal and it's much more involved.

27
00:01:57,850 --> 00:02:04,800
And as&nbsp;I already said, these things come with significant risks that you really need to be aware of and&nbsp;monitoring.

28
00:02:04,800 --> 00:02:10,055
I'll explain those shortly, but let's start 
with a quick overview of what this thing&nbsp;is.

29
00:02:10,055 --> 00:02:14,729
There are several types of these things on the market, 
but most of them are similar to this one.

30
00:02:14,729 --> 00:02:21,230
Inside is simply a fan which blows air 
through this wet pad made of absorbent material.

31
00:02:21,230 --> 00:02:26,670
The whole&nbsp;thing is mounted to a giant hole 
cut into my HVAC system's duct work.

32
00:02:26,670 --> 00:02:32,225
And when it's running, the&nbsp;fan draws in some of the air coming up from the furnace through the sides here

33
00:02:32,225 --> 00:02:37,883
and then forces&nbsp;it through that wet pad where it will absorb moisture before rejoining the airstream

34
00:02:37,883 --> 00:02:40,150
and getting&nbsp;distributed throughout my home.

35
00:02:40,150 --> 00:02:42,249
It's quite a simple device.

36
00:02:42,249 --> 00:02:44,365
Where's the water coming from?

37
00:02:44,365 --> 00:02:46,272
It's&nbsp;coming from right here.

38
00:02:46,272 --> 00:02:53,052
When the humidifier is running, this solenoid valve opens 
and a small but&nbsp;steady stream of water is fed through this line

39
00:02:53,052 --> 00:02:58,171
and up to this nozzle where it's then distributed&nbsp;
through these drip holes and onto the pad.

40
00:02:58,171 --> 00:03:00,443
That makes the pad soaking wet.

41
00:03:00,443 --> 00:03:05,197
And in fact, once it's&nbsp;saturated, 
you'll see a trickle of water coming out the bottom.

42
00:03:05,197 --> 00:03:10,520
The valve is deliberately letting&nbsp;more water through 
than the air going through the pad can absorb.

43
00:03:10,520 --> 00:03:14,322
So, you invariably end up with&nbsp;some wasted water.

44
00:03:14,322 --> 00:03:17,331
I couldn't tell you exactly how much water is being lost here,

45
00:03:17,331 --> 00:03:23,215
but I can tell&nbsp;you I have never noticed an increase 
in my water bill between heating and cooling seasons.

46
00:03:23,215 --> 00:03:25,048
So, it's&nbsp;not that much.

47
00:03:25,048 --> 00:03:30,514
But if you're concerned about that, there are water-saving models available which&nbsp;don't work like this one does.

48
00:03:30,514 --> 00:03:34,119
But, they have other considerations 
which I'm not going to be&nbsp;getting into today.

49
00:03:34,119 --> 00:03:41,261
Since the pad is essentially always soaking wet, 
it gets pretty gross and needs&nbsp;regular replacement.

50
00:03:41,261 --> 00:03:47,430
How often you'll need to do that depends largely on 
your water hardness and&nbsp;how large your home is.

51
00:03:47,430 --> 00:03:50,843
I have a fairly small home, so this thing doesn't run that much

52
00:03:50,843 --> 00:03:55,094
and&nbsp;I can usually get away with changing 
it at the start of each heating season.

53
00:03:55,094 --> 00:04:00,548
But even still, this&nbsp;is what last year's pad looks like.

54
00:04:00,548 --> 00:04:06,583
It used to be white and now it's pink and crunchy because of all&nbsp;the calcium it's filled with.

55
00:04:06,583 --> 00:04:08,691
Delicious!

56
00:04:08,691 --> 00:04:12,414
But it can be much worse than simply getting a little&nbsp;gross.

57
00:04:12,414 --> 00:04:16,459
Remember that thing I said about these needing much more attention than you might expect?

58
00:04:16,459 --> 00:04:21,241
Well, one day I heard the water valve open, but I didn't hear the fan start up.

59
00:04:21,241 --> 00:04:30,068
And that was because&nbsp;the pad had started to deteriorate and part of it fell forward and into the fan blades, holding&nbsp;them stationary.

60
00:04:30,068 --> 00:04:36,874
I'm honestly quite lucky that it didn't cause any damage to my furnace because the&nbsp;water valve was still open and getting it wet.

61
00:04:36,874 --> 00:04:43,544
So, the pad's detached section leaning at a wonky&nbsp;angle could easily have started dripping water down into the furnace.

62
00:04:43,544 --> 00:04:50,789
And when I was a little&nbsp;kid, my mom and dad had that exact thing happen which fried the furnace's control board.

63
00:04:50,789 --> 00:04:53,460
So,&nbsp;yeah, these are not set and forget -

64
00:04:53,460 --> 00:04:58,804
you really need to be cognizant of their operation and&nbsp;
needs and should be checking on it regularly.

65
00:04:59,520 --> 00:05:04,221
But anyway, you'll notice that the water line&nbsp;
is being fed by my water heater.

66
00:05:04,221 --> 00:05:09,972
This style of humidifier generally works better when the water&nbsp;
which is saturating the pad is hot.

67
00:05:09,972 --> 00:05:16,329
In fact, the manufacturer claims it needs hot water&nbsp;
if you're going to use this humidifier...

68
00:05:16,329 --> 00:05:19,007
Well, hold on. That part comes later.

69
00:05:19,007 --> 00:05:26,168
Now, since this&nbsp;is just a fan that grabs some air from the duct, gets it moist, and then puts it back into&nbsp;the duct,

70
00:05:26,168 --> 00:05:31,389
it relies on the furnace pushing air through the duct work in order to distribute&nbsp;its work

71
00:05:31,389 --> 00:05:34,769
and actually increase the humidity in my home.

72
00:05:34,769 --> 00:05:41,196
And that means if it were for some reason&nbsp;
running when the furnace's blower wasn't,

73
00:05:41,196 --> 00:05:44,238
well, it would pretty quickly cause a problem.

74
00:05:44,238 --> 00:05:52,012
The&nbsp;air in that duct work would get extremely humid and water would start condensing onto things&nbsp;which ought not get wet.

75
00:05:52,012 --> 00:05:54,430
Luckily, there's an easy solution to that:

76
00:05:54,430 --> 00:06:00,277
only power this thing up if&nbsp;the furnace is running 
and blowing air through the ducts.

77
00:06:00,277 --> 00:06:03,535
That water valve is powered by 24 volts AC,

78
00:06:03,535 --> 00:06:10,602
the same power that your furnace or air handler produces to send through your thermostat wiring&nbsp;for control signaling.

79
00:06:10,602 --> 00:06:15,528
The humidifier is also plugged into 
120 volt line voltage for its fan&nbsp;motor,

80
00:06:15,528 --> 00:06:21,988
but the fan is controlled via a current sensing relay which detects that the water valve&nbsp;is open.

81
00:06:21,988 --> 00:06:25,911
So if the water valve is open, the fan will run.

82
00:06:25,911 --> 00:06:34,294
This ultimately means if you wire that&nbsp;water valve across the common wire and the heat signal wire coming from the thermostat,

83
00:06:34,294 --> 00:06:40,499
then the&nbsp;humidifier will only be able to operate 
when your thermostat is calling for heat.

84
00:06:40,499 --> 00:06:45,123
This setup not&nbsp;only ensures the blower 
will be running when the humidifier is on,

85
00:06:45,123 --> 00:06:49,254
but it also means the humidifier&nbsp;
won't run during a cooling call.

86
00:06:49,254 --> 00:06:53,721
So, if you forget to switch it off at the end 
of the heating season,&nbsp;it's no big deal.

87
00:06:53,721 --> 00:06:57,687
But the humidifier can't simply run whenever the heat's on.

88
00:06:57,687 --> 00:07:04,607
That would likely&nbsp;result in over-humidification, which could be uncomfortable or even cause mold issues.

89
00:07:04,607 --> 00:07:11,738
So rather&nbsp;than hook the water valve to the furnace directly, 
its power wire goes through this humidistat.

90
00:07:11,738 --> 00:07:13,505
This&nbsp;is a fully analog doodad

91
00:07:13,505 --> 00:07:20,547
which sits in the return air stream and closes a switch when the humidity&nbsp;is lower than your desired set point.

92
00:07:20,547 --> 00:07:27,167
So long as that switch is closed and the thermostat 
is&nbsp;calling for heat, then the humidifier will run.

93
00:07:27,167 --> 00:07:32,273
But once the humidifier has elevated humidity&nbsp;
to your set point, that switch will open

94
00:07:32,273 --> 00:07:36,672
and the humidifier will shut off 
even if the heat is still&nbsp;running.

95
00:07:36,672 --> 00:07:39,872
It's a very simple control setup, but it works great!

96
00:07:39,872 --> 00:07:42,188
Except for when it doesn't.

97
00:07:42,188 --> 00:07:50,110
First&nbsp;of all, you may remember from a previous video of mine that my home's furnace is oversized by nearly&nbsp;a factor of four.

98
00:07:50,110 --> 00:07:54,888
This means on most days, 
it only runs for two, maybe 3 hours.

99
00:07:54,888 --> 00:07:59,729
And that's not enough&nbsp;time 
for the humidifier to actually be effective.

100
00:07:59,729 --> 00:08:04,580
That's a problem specific to my home, but it was&nbsp;very annoying.

101
00:08:04,580 --> 00:08:12,344
I couldn't get the indoor humidity to even touch 40% 
when I wanted it closer to 45 or&nbsp;even 50.

102
00:08:12,344 --> 00:08:15,359
However, there was a fix for this issue.

103
00:08:15,359 --> 00:08:22,704
Instead of hooking the humidifier's water valve&nbsp;
to the heat signal wire, I changed it to the fan signal wire.

104
00:08:22,704 --> 00:08:27,976
This meant the humidifier was able&nbsp;
to run so long as my thermostat was calling for the blower fan.

105
00:08:27,976 --> 00:08:34,560
And by setting a fan schedule on&nbsp;my thermostat, 
which ensured the fan ran for 15 minutes every hour,

106
00:08:34,560 --> 00:08:37,937
my humidifier was actually&nbsp;able to do its job.

107
00:08:37,937 --> 00:08:43,184
And for the last couple of years, 
I've been enjoying delightfully moist air&nbsp;in the winter,

108
00:08:43,184 --> 00:08:46,453
nice and comfy and free of static shocks.

109
00:08:46,453 --> 00:08:51,974
This scenario is why the manufacturer&nbsp;
wants this thing hooked to hot water.

110
00:08:51,974 --> 00:08:59,581
If it's running during a heating call, the air the&nbsp;humidifier is taking from the furnace and blowing past the pad will be hot,

111
00:08:59,581 --> 00:09:02,081
which will help water to&nbsp;evaporate.

112
00:09:02,081 --> 00:09:09,141
But if it's running during a fan call, that air is only at room temperature and the&nbsp;water won't evaporate as quickly.

113
00:09:10,390 --> 00:09:15,201
Honestly though, I have a hunch it would actually work fine if it&nbsp;
were hooked up to cold water,

114
00:09:15,201 --> 00:09:22,864
and the real reason they want it hooked to hot water is to minimize&nbsp;the cooling which would occur as water evaporates.

115
00:09:22,864 --> 00:09:28,981
This thing is basically a swamp cooler and it will&nbsp;
drop the temperature of the air leaving the vents if it's running.

116
00:09:28,981 --> 00:09:35,782
But if the pad is soaked in hot&nbsp;water, that cooling effect is diminished somewhat and possibly even eliminated.

117
00:09:35,782 --> 00:09:37,584
But anyway, that's&nbsp;not important.

118
00:09:37,584 --> 00:09:42,001
What is important is this little 
note you may have spotted on the humidistat.

119
00:09:42,001 --> 00:09:47,873
This&nbsp;thing wants you to turn the humidity 
set point down as the outdoor temperature falls.

120
00:09:47,873 --> 00:09:54,722
This is&nbsp;because the colder it is outside, the colder the inside surface of your walls and windows becomes

121
00:09:54,722 --> 00:09:57,731
and that will encourage condensation.

122
00:09:57,731 --> 00:10:02,433
This could simply be an inconvenience - maybe you'll have some&nbsp;water puddling on window sills.

123
00:10:02,433 --> 00:10:07,042
But it could also lead to mold growth 
inside your exterior walls.

124
00:10:07,327 --> 00:10:11,091
And you don't want that, 
which is why it has this helpful little note.

125
00:10:11,091 --> 00:10:14,676
There's just one small&nbsp;problem with notes like this, though.

126
00:10:14,676 --> 00:10:20,146
You're lucky if people read them, and you're even luckier&nbsp;if people remember about them.

127
00:10:20,146 --> 00:10:23,819
I'm a people and I have forgotten about this several times.

128
00:10:23,819 --> 00:10:29,900
Usually&nbsp;what happens is the temperature plummets overnight and when I get up, the windows are soaking wet.

129
00:10:29,900 --> 00:10:32,806
So&nbsp;then I go downstairs to the furnace closet -

130
00:10:32,806 --> 00:10:35,000
quick reminder for you homebuilders out there,

131
00:10:35,000 --> 00:10:36,946
this can&nbsp;all just go in a closet!

132
00:10:36,946 --> 00:10:39,893
It never has to go in an attic.

133
00:10:39,893 --> 00:10:42,836
If you're doing that, you suck at planning!

134
00:10:42,836 --> 00:10:48,477
And I promise everybody out there, the 20 square feet 
or so taken up by this stuff in the floor&nbsp;plan

135
00:10:48,477 --> 00:10:52,733
is absolutely worth being able to get at it without a ladder.

136
00:10:52,733 --> 00:10:53,892
Priorities, man.

137
00:10:53,892 --> 00:10:55,107
Get some!

138
00:10:55,856 --> 00:11:00,941
As I&nbsp;was saying, I go downstairs to the furnace closet, 
turn this down, and then when the cold snap is&nbsp;over,

139
00:11:00,941 --> 00:11:03,958
I'll wonder why it's not as 
comfortable as I'd like it to be before remembering,

140
00:11:03,958 --> 00:11:07,793
"Oh right,&nbsp;I turned the humidistat down"
and then I turn it back up.

141
00:11:07,793 --> 00:11:14,370
Given all that hassle, it sure would&nbsp;be nice if there were humidistats out there that were aware of the outdoor temperature

142
00:11:14,370 --> 00:11:20,332
and could&nbsp;automatically adjust the indoor 
humidity set point down during those cold snaps.

143
00:11:20,332 --> 00:11:22,648
Oh, wait.&nbsp;Those exist!

144
00:11:22,648 --> 00:11:29,453
But, well gosh darn it, they're going to 
need a wire run to an outdoor temperature&nbsp;sensor.

145
00:11:29,453 --> 00:11:33,772
And this furnace closet is 
pretty much in the dead center of my home.

146
00:11:33,772 --> 00:11:35,786
So, that's gonna be&nbsp;annoying.

147
00:11:35,786 --> 00:11:42,310
The easiest thing to do would be to run a wire across the garage and maybe slip it past&nbsp;the garage door seal,

148
00:11:42,310 --> 00:11:50,863
but I didn't like that idea, and I really didn't like the idea of drilling&nbsp;holes in walls or having random wires going all over the place.

149
00:11:50,863 --> 00:11:53,367
I've lived in my home for over three&nbsp;years now

150
00:11:53,367 --> 00:11:59,200
and have been lamenting the difficulty of installing an outdoor temp sensor for a&nbsp;better humidistat the whole time.

151
00:11:59,200 --> 00:12:05,120
And then about two weeks ago, I finally remembered about that&nbsp;
pipe that brings in outside air for the furnace.

152
00:12:05,680 --> 00:12:09,485
Yeah, this pipe here, it goes all the way outside.

153
00:12:09,485 --> 00:12:15,822
The point of this is to allow the furnace to have combustion air without creating negative pressure&nbsp;in the building.

154
00:12:15,822 --> 00:12:21,717
When this panel is closed up, 
the combustion section of this furnace is effectively&nbsp;outdoors.

155
00:12:21,717 --> 00:12:27,000
It draws in fresh air through here, which brings in 
enough oxygen to set some methane&nbsp;on fire

156
00:12:27,000 --> 00:12:31,043
and then pushes the exhaust gases out this other pipe.

157
00:12:31,043 --> 00:12:36,945
And uh well, I could have just run&nbsp;
the outdoor sensor wire through this pipe the whole time.

158
00:12:37,980 --> 00:12:40,319
Yeah, better late than never!

159
00:12:40,319 --> 00:12:46,927
Now,&nbsp;quick note, some of the fancier 
thermostats out there are able to control a humidifier directly.

160
00:12:46,927 --> 00:12:51,626
I&nbsp;don't have one of those - I just have a basic Nest
which irritates me for several reasons,

161
00:12:51,626 --> 00:12:55,036
but&nbsp;mostly works and I somewhat begrudgingly put up with.

162
00:12:55,036 --> 00:13:01,834
Luckily, the people who built my home&nbsp;were kind enough to not cheap out and actually ran seven conductor thermostat wire

163
00:13:01,834 --> 00:13:04,559
between my&nbsp;furnace and the thermostat.

164
00:13:04,559 --> 00:13:09,734
And this means I could upgrade 
to a fancier Nest or some other smart&nbsp;thermostat

165
00:13:09,734 --> 00:13:15,660
which knows the outside temperature
 through the internet and then allowed it to&nbsp;control the humidifier.

166
00:13:15,660 --> 00:13:20,303
But quite frankly, I am trusting 
internet-based solutions less and less&nbsp;these days.

167
00:13:20,303 --> 00:13:22,715
So, I decided not to go that route.

168
00:13:22,715 --> 00:13:26,384
Instead, I searched for a new dedicated&nbsp;humidistat.

169
00:13:26,384 --> 00:13:31,829
And then I discovered, wow, 
this is a much rarer product than I imagined.

170
00:13:31,829 --> 00:13:33,879
I mean, in hindsight, I kind of get it.

171
00:13:33,879 --> 00:13:37,110
When you buy a humidifier, it's going to come with one&nbsp;of these.

172
00:13:37,110 --> 00:13:42,409
But my humidifier apparently came with 
this dumb one, and I want a smarter one.

173
00:13:42,409 --> 00:13:49,022
And&nbsp;since apparently nobody but specialty supply houses stocks these things, off to Amazon I&nbsp;went.

174
00:13:49,022 --> 00:13:52,821
I found this Honeywell model as well as this Aprilaire model

175
00:13:52,821 --> 00:13:56,346
and this suspicious clone of&nbsp;the Aprilaire model.

176
00:13:56,346 --> 00:14:02,519
Since I have an Aprilaire 700 series 
and this claims to be compatible with that&nbsp;humidifier,

177
00:14:02,519 --> 00:14:06,183
I figured I'll just get the Aprilaire 60 humidity control.

178
00:14:06,183 --> 00:14:07,677
So I did.

179
00:14:07,677 --> 00:14:15,165
Annoyingly,&nbsp;the product listing gave no information on how long the outdoor air temperature sensor&nbsp;wire was.

180
00:14:15,165 --> 00:14:22,434
I'd need about 30 feet of wire and I figured it would be reasonable for them to&nbsp;include perhaps 50 feet of wire.

181
00:14:22,434 --> 00:14:25,595
But nope, it was about 2 feet long.

182
00:14:25,595 --> 00:14:29,065
No big deal. I have a&nbsp;soldering iron and I know how to use it.

183
00:14:29,065 --> 00:14:32,508
So, the first step was to run a wire through that pipe.

184
00:14:32,508 --> 00:14:39,089
I&nbsp;made a stop at everybody's favorite suspiciously cheap tool store and got myself a suspiciously&nbsp;cheap 50-ft fishtape.

185
00:14:39,089 --> 00:14:42,567
I'm sorry, no, it's a 50 Fish T ape.

186
00:14:43,459 --> 00:14:47,989
I tried to run the fishtape directly&nbsp;
through where the pipe ends inside the furnace,

187
00:14:47,989 --> 00:14:53,295
but I wasn't too hopeful that that would work 
as&nbsp;there's a lot of bendy bendy in those pipes.

188
00:14:53,295 --> 00:14:55,758
And indeed, it didn't work.

189
00:14:55,758 --> 00:15:00,058
No big deal. I figured&nbsp;I'd just drill a hole in this last 90 here,

190
00:15:00,058 --> 00:15:05,360
which was probably the start of a straight shot&nbsp;
all the way to where the pipe comes out the wall.

191
00:15:05,920 --> 00:15:11,958
After double and triple-checking that I was about&nbsp;
to drill through the intake pipe and not the&nbsp;exhaust pipe,

192
00:15:11,958 --> 00:15:13,247
I made my hole.

193
00:15:13,247 --> 00:15:19,727
And the fishtape&nbsp;went in nice and smooth 
for a good long while, but then it hit something.

194
00:15:19,727 --> 00:15:23,866
I tried and tried and&nbsp;wiggled and wiggled, 
but it was just not going to budge.

195
00:15:23,866 --> 00:15:25,816
That was annoying.

196
00:15:25,816 --> 00:15:29,179
But then I remembered&nbsp;
a trick I saw on the internet somewhere.

197
00:15:29,179 --> 00:15:34,835
I took some lightweight twine and tied it to the end of&nbsp;a shopping bag, and then I stuffed it into the pipe.

198
00:15:34,835 --> 00:15:40,879
Then I went outside with my vacuum cleaner,&nbsp;
which had an attachment that fit nearly perfectly into that pipe

199
00:15:40,879 --> 00:15:42,916
and gave it a toot.

200
00:15:42,916 --> 00:15:48,544
I am terribly&nbsp;sorry that I left my mic kit plugged into the camera because there's no sound for this clip, \

201
00:15:48,544 --> 00:15:51,296
but&nbsp;I'll dub it with what I imagine it sounded like.

202
00:15:51,296 --> 00:15:53,095
[fwbbslrpptty-yoop]

203
00:15:54,000 --> 00:15:58,246
I honestly could not believe 
how well&nbsp;that worked, but I was sure glad it did.

204
00:15:58,246 --> 00:16:00,767
Too bad I already drilled that hole, I&nbsp;guess.

205
00:16:00,767 --> 00:16:07,860
With the bag and the twine now at the other end of the pipe, I pulled it out&nbsp;and tied a wire to the end of the twine.

206
00:16:07,860 --> 00:16:14,587
I wasn't planning to use speaker wire for this, but since&nbsp;
this pipe is apparently twistier than I realized,

207
00:16:14,587 --> 00:16:17,895
I wanted something relatively thick and strong.

208
00:16:17,895 --> 00:16:21,498
Then I went back inside and started pulling on the twine.

209
00:16:21,498 --> 00:16:24,375
It was going so well, but then...

210
00:16:25,374 --> 00:16:26,132
But!

211
00:16:26,132 --> 00:16:27,648
A Christmas miracle!

212
00:16:27,648 --> 00:16:32,370
It made it past that hole I drilled, 
and with some picks, I was able to get&nbsp;it out.

213
00:16:32,370 --> 00:16:34,857
Good thing I already drilled that hole, I guess.

214
00:16:34,857 --> 00:16:37,933
I pulled out about 10 ft of wire from that&nbsp;hole,

215
00:16:37,933 --> 00:16:43,926
and then I went outside, cut it to length, 
and soldered the sensor wire to the new end I&nbsp;just made.

216
00:16:43,926 --> 00:16:51,385
Then I went back inside and pulled the wire back until the sensor was dangling down&nbsp;at the very end of the intake pipe.

217
00:16:51,385 --> 00:16:53,988
And that's where I decided to leave it.

218
00:16:53,988 --> 00:17:00,773
Then I taped the wire&nbsp;in place and made a 
big ol' booger of silicone to seal up that hole in the pipe.

219
00:17:00,773 --> 00:17:03,988
Now, some of you,&nbsp;
including the writers of the instruction manual,

220
00:17:03,988 --> 00:17:11,966
might be concerned about how close the intake&nbsp;pipe is to the exhaust pipe, but I am confident that this location is fine.

221
00:17:11,966 --> 00:17:18,480
For one, when the&nbsp;furnace is running, it will be drawing fresh air up and through the tube past the sensor,

222
00:17:18,480 --> 00:17:20,725
so the heat from the exhaust shouldn't matter.

223
00:17:21,440 --> 00:17:26,481
My water heater exhaust is also in this area,&nbsp;
which could potentially affect it.

224
00:17:26,481 --> 00:17:33,780
But unless I'm actually using hot water, the water heater&nbsp;only comes on for about 5 minutes every few hours&nbsp;or so.

225
00:17:33,780 --> 00:17:36,733
And one day, I want to get a heat pump&nbsp;water heater.

226
00:17:36,733 --> 00:17:43,437
I could have, of course, actually pulled the wire out of the bottom of that pipe and&nbsp;mounted the sensor somewhere if I were concerned,

227
00:17:43,437 --> 00:17:45,335
but I wasn't, so I didn't.

228
00:17:45,335 --> 00:17:50,795
All right, with the&nbsp;outdoor temp sensor in place, 
it was time to install the new humidistat.

229
00:17:50,795 --> 00:17:56,026
It needs a 3/4 inch&nbsp;hole 
in the return duct to get a measurement of relative humidity.

230
00:17:56,026 --> 00:18:00,506
And I was hopeful the existing&nbsp;
humidistat would have a similar hole underneath,

231
00:18:00,506 --> 00:18:08,049
but no, that one needed a big old hole cut in&nbsp;
the sheet metal, which now presented me with a problem.

232
00:18:08,049 --> 00:18:13,594
I elected to seal that hole with some&nbsp;
duct tape and mount the new humidistat lower down.

233
00:18:13,594 --> 00:18:20,527
I didn't have a 3/4 inch drill bit, so I simply&nbsp;abused my 1/2 inch drill bit and made this beautiful hole.

234
00:18:20,527 --> 00:18:26,641
But with it mounted here, it will now be&nbsp;able to know the humidity of the air which is entering my furnace.

235
00:18:26,641 --> 00:18:30,598
This is something that I&nbsp;don't quite love about this humidistat.

236
00:18:30,598 --> 00:18:32,907
For my home, it's perfect.

237
00:18:32,907 --> 00:18:36,669
I don't actually have any&nbsp;return ducting at all.

238
00:18:36,669 --> 00:18:43,388
The enclosed bedrooms upstairs have vents installed above the doors&nbsp;which pass air into the hallway.

239
00:18:43,388 --> 00:18:49,251
And the hallway leads to a switchback staircase which goes all&nbsp;the way down to the lower level where the furnace is.

240
00:18:49,251 --> 00:18:55,923
And since the main level is basically one big&nbsp;
room, the staircase itself is the return air path

241
00:18:55,923 --> 00:19:01,116
and all the furnace needs is one 
giant intake vent&nbsp;at the bottom of the stairs.

242
00:19:01,116 --> 00:19:05,661
That's what's on the other side of the duct 
I've just attached the&nbsp;control to.

243
00:19:05,661 --> 00:19:12,928
My home's setup means that whenever the furnace blower is running, the humidistat is&nbsp;going to get a pretty accurate reading.

244
00:19:12,928 --> 00:19:19,868
But I can think of plenty of cases where it would be better&nbsp;
for the humidity sensor to be somewhere else.

245
00:19:19,868 --> 00:19:26,956
In those cases, you might be better off getting a&nbsp;
fancier thermostat, which can control a humidifier remotely.

246
00:19:26,956 --> 00:19:31,708
But if your home's HVAC system was&nbsp;
designed reasonably well like mine was,

247
00:19:31,708 --> 00:19:37,232
taking a reading of the air entering 
the furnace or air&nbsp;handler should work fine.

248
00:19:37,232 --> 00:19:41,029
And with it now mounted, all that was left was the wiring.

249
00:19:41,029 --> 00:19:44,318
Here, things are&nbsp;drastically different than before.

250
00:19:44,318 --> 00:19:49,055
This humidistat has the capability 
to force the furnace fan to&nbsp;run.

251
00:19:49,055 --> 00:19:55,467
If it hasn't gotten a heating call in an hour, it will kick on the blower so it can stir&nbsp;the air up for a while,

252
00:19:55,467 --> 00:20:02,125
get an accurate humidity reading, and then if it's too low, it will switch&nbsp;the humidifier on and keep the blower running

253
00:20:02,125 --> 00:20:05,287
regardless of what the thermostat's commanding.

254
00:20:05,287 --> 00:20:10,891
This is a pretty neat feature, and it means 
I can remove the fan schedule from my thermostat.

255
00:20:10,891 --> 00:20:15,019
But&nbsp;it also means this now needs a way to control the furnace.

256
00:20:15,019 --> 00:20:20,179
But in addition to that, it also wants to&nbsp;
know if the thermostat is calling for heat.

257
00:20:20,179 --> 00:20:23,745
So it needs some pretty significant wiring changes.

258
00:20:23,745 --> 00:20:30,157
In fact, it wants to be connected to R and C, giving it a 24 volt power source from the furnace,

259
00:20:30,157 --> 00:20:33,437
W so it can see a heating call in progress,

260
00:20:33,437 --> 00:20:38,640
and it wants me to disconnect the thermostat wire&nbsp;
from the G terminal on the furnace

261
00:20:38,640 --> 00:20:42,494
and instead connect it to the G terminal on the humidistat.

262
00:20:42,494 --> 00:20:50,364
Then I need to run a new G wire called Gf back from the humidistat and land it on the G terminal&nbsp;in the furnace.

263
00:20:50,364 --> 00:20:54,234
This setup is what allows the humidistat 
to force the furnace blower on,

264
00:20:54,234 --> 00:20:58,906
but&nbsp;it will still pass a fan call 
from the thermostat through as normal.

265
00:20:58,906 --> 00:21:05,197
And finally, of course, I need&nbsp;to connect the humidifier's control wires to the two H terminals on the board

266
00:21:05,197 --> 00:21:07,663
and the outdoor&nbsp;temperature sensor.

267
00:21:07,663 --> 00:21:12,558
With that done, all that was needed 
was to turn the furnace back on and&nbsp;test it out.

268
00:21:12,558 --> 00:21:13,855
Hope I didn't blow anything up.

269
00:21:16,567 --> 00:21:21,445
[blower noise in background]
I think the outdoor temperature is high&nbsp;enough for it to run

270
00:21:21,445 --> 00:21:24,336
if I turn it to six, but we'll see.

271
00:21:24,836 --> 00:21:25,896
[click]

272
00:21:26,860 --> 00:21:30,939
Uhhh, so the board woke up and the&nbsp;relay definitely clicked

273
00:21:30,939 --> 00:21:35,728
and it's telling me the humidifier is running, 
but the humidifier is not&nbsp;actually running.

274
00:21:36,656 --> 00:21:38,282
Well...

275
00:21:38,282 --> 00:21:43,289
All right, with the help of a multimeter and some troubleshooting, I have&nbsp;figured out what's going on here.

276
00:21:43,289 --> 00:21:45,709
And now I'm mad!

277
00:21:45,709 --> 00:21:53,567
So, this thing comes with instructions for hooking&nbsp;it up to an Aprilaire 700 series humidifier, which is what I have.

278
00:21:53,567 --> 00:21:57,936
And it has a footnote about 
if&nbsp;your humidifier was made before 2007

279
00:21:57,936 --> 00:22:01,830
(apparently they've been making them like these forever) 
there's some difference in the wiring.

280
00:22:01,830 --> 00:22:05,423
Well, this humidifier is definitely 
newer than that,&nbsp;but it's not working.

281
00:22:05,423 --> 00:22:10,713
Well, it turns out I don't have a 700. I have a 700M.

282
00:22:10,713 --> 00:22:13,554
And you would&nbsp;think, right, the M stands for manual -

283
00:22:13,554 --> 00:22:20,900
the only difference between those models is you get the&nbsp;
manual control, the one that I just replaced, or this digital control.

284
00:22:20,900 --> 00:22:27,338
But in fact, the 700M&nbsp;
gets its 24volts AC externally from the furnace.

285
00:22:27,338 --> 00:22:32,403
And the 700 automatic version 
has its own 24 volt&nbsp;transformer inside.

286
00:22:32,403 --> 00:22:37,682
And all this is doing is bridging 
these two contacts through this&nbsp;relay.

287
00:22:37,682 --> 00:22:44,535
But the manual humidifier needs to get 24 volts AC, 
which is going to be possible with this -

288
00:22:44,535 --> 00:22:48,909
I have to do a little bit of sanity checking 
to make sure I wire it correctly.

289
00:22:48,909 --> 00:22:55,042
But I'm going&nbsp;to have to jump either 
R or C over to one side of this

290
00:22:55,042 --> 00:23:02,531
and then basically have that relay send&nbsp;
24 volts up to the humidifier like the original control.

291
00:23:02,531 --> 00:23:08,753
Now, why on earth does Aprilaire 
choose&nbsp;to distinguish them in this way?

292
00:23:08,753 --> 00:23:10,993
I don't know, but it's really frustrating.

293
00:23:10,993 --> 00:23:17,605
And they clearly&nbsp;don't want people figuring out how to wire this digital version to the manual one

294
00:23:17,605 --> 00:23:19,342
because&nbsp;they just don't even tell you it's possible.

295
00:23:19,342 --> 00:23:21,964
But it's totally possible. This is just a relay.

296
00:23:21,964 --> 00:23:27,182
One of these relays does the humidifier. 
The other relay forces the furnace fan on.

297
00:23:27,182 --> 00:23:34,768
But they&nbsp;do not give you a wiring diagram for how to use this with the manual model, even though it's&nbsp;completely possible.

298
00:23:35,767 --> 00:23:39,975
[sigh]
I've been meaning to make a video on right to repair for a while.

299
00:23:39,975 --> 00:23:44,660
This isn't&nbsp;quite part of that, but man.

300
00:23:44,660 --> 00:23:45,810
This is dumb.

301
00:23:45,810 --> 00:23:48,295
Okay, my modifications are complete.

302
00:23:48,295 --> 00:23:53,993
Now, this is&nbsp;going to look very confusing because I don't have - almost none of these wire colors are correct.

303
00:23:53,993 --> 00:23:57,252
I'm&nbsp;actually using garage door opener sensor wire.

304
00:23:57,252 --> 00:23:59,699
Uh, yeah, but it should work.

305
00:23:59,699 --> 00:24:06,070
Basically, I now have red and blue 
(this is 24 volts and common)

306
00:24:06,070 --> 00:24:10,746
taken off of the input and then I have a separate lead&nbsp;for them.

307
00:24:10,746 --> 00:24:17,122
So now this thing and the humidifier are wired in parallel.

308
00:24:17,122 --> 00:24:23,505
But the humidifier's&nbsp;return - 
it's landing on one of the H terminals

309
00:24:23,505 --> 00:24:26,437
and then the other H terminal 
is coming back to&nbsp;this common point.

310
00:24:26,437 --> 00:24:33,708
So basically the humidifier 
would run all the time if this relay is closed.

311
00:24:33,708 --> 00:24:37,271
But when the relay is open it shouldn't run.

312
00:24:38,960 --> 00:24:45,435
Now, there's really nothing left to do except&nbsp;
turn this back on and hope for the best.

313
00:24:45,435 --> 00:24:51,434
Now, uh I know it's safe to do this because the&nbsp;
worst thing that would happen

314
00:24:51,434 --> 00:24:55,283
is I will blow the furnace's power supply fuse.

315
00:24:55,283 --> 00:24:58,987
And uh it's&nbsp;probably an automotive fuse,
I may even have a spare on hand.

316
00:24:58,987 --> 00:25:02,248
But it will be easy to&nbsp;get a replacement if I need it.

317
00:25:02,248 --> 00:25:07,328
It's part of how I know it's safe 
for me to be doing this&nbsp;nonsense.

318
00:25:07,328 --> 00:25:11,804
Here is the moment of truth, part two.

319
00:25:16,479 --> 00:25:18,743
Okay, it's on.

320
00:25:18,743 --> 00:25:20,941
We're going blower activation...

321
00:25:23,725 --> 00:25:26,094
I'm going to turn that to on.

322
00:25:26,094 --> 00:25:29,197
Crank this up all&nbsp;the way and hopefully the humidifier comes on.

323
00:25:31,766 --> 00:25:33,149
What is this test?

324
00:25:33,149 --> 00:25:37,042
[clack, hissing, whirring] 
Oh, well, that works.

325
00:25:37,042 --> 00:25:39,815
And look&nbsp;at that! The humidifier is running!

326
00:25:39,815 --> 00:25:41,453
Now, is the blower actually running?

327
00:25:41,453 --> 00:25:44,034
It's hard to tell when&nbsp;the humidifier is on as well.

328
00:25:44,034 --> 00:25:47,372
Oh, for sure it is. So, that worked correctly.

329
00:25:48,407 --> 00:25:50,760
Want to make sure this&nbsp;actually shuts off now.

330
00:25:50,938 --> 00:25:52,464
[clunk]

331
00:25:52,786 --> 00:25:53,653
Awesome.

332
00:25:53,653 --> 00:26:01,165
With that rather ugly but functional wiring modification, 
this is&nbsp;now working as I expected it to the whole time.

333
00:26:01,165 --> 00:26:05,588
The humidistat can now energize this relay, 
which&nbsp;forces the furnace fan to run.

334
00:26:05,588 --> 00:26:10,966
And that allows it to perform its own check 
of the ambient humidity&nbsp;level on an hourly basis.

335
00:26:10,966 --> 00:26:16,789
If during that check it finds that it's lower than the set point, it will&nbsp;then energize this relay which,

336
00:26:16,789 --> 00:26:23,986
thanks to those horrible jumpers and wire nuts will now send power&nbsp;up to the humidifier's water valve, which will switch it on.

337
00:26:23,986 --> 00:26:27,148
And of course, that will increase&nbsp;the humidity in my home.

338
00:26:27,148 --> 00:26:33,791
But once it reaches the set point, the humidity sensor will detect that,&nbsp;at which point it will turn the humidifier off.

339
00:26:33,791 --> 00:26:37,436
That will all happen regardless of what my&nbsp;thermostat's doing.

340
00:26:37,436 --> 00:26:40,880
If though my thermostat is commanding the heat to run,

341
00:26:40,880 --> 00:26:47,372
the humidistat is now&nbsp;aware of that thanks to the fact that it's hooked up to the W terminal on the furnace board.

342
00:26:47,372 --> 00:26:54,342
So, as&nbsp;before, if the humidity is below the set point, it will close the relay and send power to the&nbsp;humidifier.

343
00:26:54,342 --> 00:26:58,516
And once it's satisfied, it shuts the humidifier off.

344
00:26:58,516 --> 00:27:01,549
Now, none of this is really&nbsp;new.

345
00:27:01,549 --> 00:27:05,132
My old setup with the humidifier connected to the fan terminal

346
00:27:05,132 --> 00:27:11,536
and with my thermostat&nbsp;forcing the fan to run for 15 minutes every hour accomplished the same thing.

347
00:27:11,536 --> 00:27:17,906
See, I also went into&nbsp;my thermostat's programming to make it command the fan during a heating call.

348
00:27:17,906 --> 00:27:25,280
Something that's&nbsp;not necessary for my heating system to work, but which allowed the humidifier to run during a heating call, too.

349
00:27:25,280 --> 00:27:32,026
So, when it comes to the basic functionality 
of the humidifier, I haven't really&nbsp;changed anything.

350
00:27:32,026 --> 00:27:38,639
But now that this control knows what the outdoor air temperature is, I no longer&nbsp;have to think about that.

351
00:27:38,639 --> 00:27:45,258
It will automatically reduce the humidity set point as the ambient&nbsp;temperature outside falls.

352
00:27:45,258 --> 00:27:51,637
This chart here explains how the humidifier will adjust the set&nbsp;
point based on the outdoor temperature reading.

353
00:27:51,637 --> 00:28:00,613
The recommended setting, five, will allow the&nbsp;humidity to get as high as 45%, but will start lowering it when the outdoor temp is 30° F,

354
00:28:00,613 --> 00:28:03,468
which&nbsp;is just a hair below freezing.

355
00:28:03,468 --> 00:28:10,476
I know that my home can handle 45% 
at that temperature just fine so I decided to set it to six.

356
00:28:10,476 --> 00:28:14,651
And actually, this is my biggest disappointment with this thing.

357
00:28:14,651 --> 00:28:24,472
I would&nbsp;like setting six to shoot for 50% humidity when it's above freezing outside, but the highest this&nbsp;will ever go is 45%.

358
00:28:24,472 --> 00:28:27,887
That's not a big difference, but I can notice it.

359
00:28:27,887 --> 00:28:35,188
Still, I will happily&nbsp;sacrifice that for the peace of mind that this will automatically reduce its output in those cold&nbsp;snaps.

360
00:28:35,188 --> 00:28:40,598
I haven't had this installed for very long, 
but my thermostat, which has a hygrometer in&nbsp;there,

361
00:28:40,598 --> 00:28:44,114
is telling me the indoor humidity is hovering around 45%.

362
00:28:44,114 --> 00:28:47,875
So, it's doing its job&nbsp;and seems to be accurate.

363
00:28:47,875 --> 00:28:51,824
Or I guess at least my thermostat agrees with it.

364
00:28:51,824 --> 00:28:53,960
The other thing I&nbsp;don't like about this?

365
00:28:53,960 --> 00:28:58,117
It won't tell me what it thinks the outdoor temperature is.

366
00:28:58,117 --> 00:29:05,528
It should throw&nbsp;an error code if the sensor goes bad, 
but what if the sensor is simply drifting over time?

367
00:29:05,528 --> 00:29:11,511
I'm not&nbsp;going to know that unless the drift is 
bad enough to cause it to over- or under-humidify.

368
00:29:11,511 --> 00:29:15,487
Since I've&nbsp;installed this, 
the outdoor temperature hasn't fallen much below freezing.

369
00:29:15,487 --> 00:29:19,745
So, I'm not even&nbsp;sure yet that it's working as intended.

370
00:29:19,745 --> 00:29:23,594
That's cool since, you know, 
that's the whole reason I&nbsp;did this.

371
00:29:23,594 --> 00:29:26,542
But, we're supposed to get a cold snap shortly after Christmas,

372
00:29:26,542 --> 00:29:32,034
and I'll do one of those&nbsp;community posts once we've gone through that. And I'll pin a comment here, too.

373
00:29:32,034 --> 00:29:35,149
Aside from the&nbsp;absolute ridiculousness that was

374
00:29:35,149 --> 00:29:42,014
having to figure out my own way to get this Aprilaire humidity&nbsp;controller to work with my Aprilaire humidifier,

375
00:29:42,014 --> 00:29:44,719
I am very happy to have made this upgrade.

376
00:29:44,719 --> 00:29:47,085
But&nbsp;to circle back to the beginning of this video,

377
00:29:47,085 --> 00:29:53,219
while the main point of doing this is to make my&nbsp;humidifier something closer to set-and-forget,

378
00:29:53,219 --> 00:29:56,940
it's still absolutely not set-and-forget.

379
00:29:56,940 --> 00:29:59,819
The potential for leaks is still there.

380
00:29:59,819 --> 00:30:03,877
The potential for a deteriorating water pad is still&nbsp;there.

381
00:30:03,877 --> 00:30:09,215
And while I hope its outdoor temperature sensor 
will work reliably for years to come,

382
00:30:09,215 --> 00:30:15,942
the&nbsp;potential for too much humidification 
if it starts drifting in the wrong direction is still there.

383
00:30:15,942 --> 00:30:21,821
I will absolutely still be monitoring 
my home's humidity level and the function of the humidifier.

384
00:30:21,821 --> 00:30:28,100
And I suggest that anybody out there with one of these things check on it at least monthly and&nbsp;preferably weekly.

385
00:30:28,100 --> 00:30:35,199
That I think is the biggest argument for choosing a large freestanding&nbsp;humidifier over one of these things.

386
00:30:35,199 --> 00:30:38,143
Sure, it's annoying to fill those up with water every&nbsp;day or two,

387
00:30:38,143 --> 00:30:44,997
especially considering that you'll need to use a water treatment product with those&nbsp;fill-ups to prevent odors and mold growth.

388
00:30:44,997 --> 00:30:48,068
And of course, they take up space.

389
00:30:48,068 --> 00:30:55,267
But when you have to&nbsp;keep interacting with it in order for it to keep working, you'll be more likely to notice problems.

390
00:30:55,267 --> 00:31:00,890
Plus, if its tank were to start leaking, at most you'll have a few gallons of water on the floor.

391
00:31:00,890 --> 00:31:07,175
This thing's plumbed to full water pressure, 
which means leaks could be much more catastrophic.

392
00:31:07,175 --> 00:31:11,871
I have a floor drain in this furnace closet, 
so I'm not too too worried about that.

393
00:31:11,871 --> 00:31:17,462
But still, it&nbsp;could cause 
major damage to my furnace, and that's not good.

394
00:31:17,462 --> 00:31:23,227
But I must admit, it has been very nice&nbsp;
to have this machine keeping the air comfortable

395
00:31:23,227 --> 00:31:27,220
without having to fill up a weird 
2 gallon bottle&nbsp;every couple of days.

396
00:31:27,220 --> 00:31:31,063
And now that the humidistat knows the outdoor air temperature,

397
00:31:31,063 --> 00:31:35,974
I'll be&nbsp;slightly more at peace 
knowing that I can't forget to turn it down.

398
00:31:35,974 --> 00:31:40,423
I'm still going to be checking&nbsp;on the humidifier 
every week or so to make sure the fan is spinning

399
00:31:40,423 --> 00:31:42,718
and that there isn't water&nbsp;where there shouldn't be.

400
00:31:42,718 --> 00:31:48,061
Plus, of course, I'll be checking that 
the controller I installed actually&nbsp;does its job.

401
00:31:48,061 --> 00:31:53,878
Assuming it does, though, this is as close to set-and-forget as you can reasonably&nbsp;make one of these,

402
00:31:53,878 --> 00:31:56,245
and that makes me happy.

403
00:31:57,067 --> 00:31:59,822
♫ moistenedly smooth jazz ♫

404
00:32:00,595 --> 00:32:03,624
A few things I didn't mention in the main&nbsp;body of the video:

405
00:32:03,624 --> 00:32:09,561
First, like my old setup, I'll have to remember to turn this off when the&nbsp;weather gets warm.

406
00:32:09,561 --> 00:32:14,611
If I don't, it may try to add humidity when that's the last thing I want.

407
00:32:14,611 --> 00:32:16,309
Yay,&nbsp;Midwest.

408
00:32:16,309 --> 00:32:23,833
Second, at time of filming, I haven't yet verified whether or not it knows the thermostat&nbsp;is commanding the fan.

409
00:32:23,833 --> 00:32:28,269
It should, but I didn't think to actually test that before I got here and&nbsp;shot the talking head.

410
00:32:28,269 --> 00:32:29,579
Here's the answer:

411
00:32:29,579 --> 00:32:35,110
I just confirmed that yes, it does turn on the 
humidifier&nbsp;when the thermostat gives it a fan call.

412
00:32:35,110 --> 00:32:37,455
So, that is working as I expected.

413
00:32:37,455 --> 00:32:41,538
And third, this thing's&nbsp;humidity sensor does a reasonable job,

414
00:32:41,538 --> 00:32:48,454
but I have noticed that the displayed humidity falls quite&nbsp;
dramatically as soon as I open the door to the furnace closet.

415
00:32:48,454 --> 00:32:52,716
It drops by about 5% even when the&nbsp;blower is running.

416
00:32:52,716 --> 00:32:58,285
This is a bit puzzling to me as it's in the same room 
that the furnace is pulling&nbsp;air from.

417
00:32:58,285 --> 00:33:02,663
And based on what my 
thermostat is telling me, it doesn't seem to matter.

418
00:33:02,663 --> 00:33:09,135
But clearly&nbsp;the sensor is being affected 
by the air around it and not just inside the duct.

419
00:33:09,135 --> 00:33:12,231
That makes complete&nbsp;sense based on this thing's design.

420
00:33:12,231 --> 00:33:18,320
And it would really be improved if it had some sort of remote&nbsp;sensor you could shove deep into the duct.

421
00:33:18,320 --> 00:33:24,109
Plus, that would mean you could mount this control&nbsp;
somewhere it's more visible if you wanted.

422
00:33:24,109 --> 00:33:29,911
I know there are plenty of climates out there&nbsp;where the idea of wanting to add moisture to the air is abhorrent,

423
00:33:29,911 --> 00:33:37,198
but I'm surprised how&nbsp;terrible the options seem to be 
for central ducted humidifier controls.

424
00:33:37,198 --> 00:33:40,674
They are simple&nbsp;things, yes, 
but we could be doing so much better.

425
00:33:43,422 --> 00:33:47,256
...humidistat the whole time and then about 2 weeks later -

426
00:33:47,256 --> 00:33:48,745
oh shoot.

427
00:33:48,745 --> 00:33:53,532
Yeah, it used to be white and now it's pink and chunky fer-

428
00:33:53,532 --> 00:33:55,884
ah, it's crunchy!

429
00:33:55,884 --> 00:33:57,469
Crunchy,&nbsp;not chunky.

430
00:33:57,469 --> 00:33:58,655
Eurgh.

431
00:33:58,655 --> 00:34:04,926
This thing is basically a swamp cooler and will drop the temperature of the air&nbsp;leaving the vents if it's running.

432
00:34:04,926 --> 00:34:07,140
But the pad...

433
00:34:09,520 --> 00:34:11,318
I missed the word if.

434
00:34:12,174 --> 00:34:15,199
Then I&nbsp;taped the wire in place and made a...

435
00:34:15,199 --> 00:34:16,687
ah, farts.

436
00:34:16,687 --> 00:34:19,646
That's what's on&nbsp;the other side of the duct of...

437
00:34:19,646 --> 00:34:20,477
Farts.

438
00:34:20,477 --> 00:34:21,615
Farts!!

439
00:34:23,578 --> 00:34:30,195
So those of you who were looking at that wiring diagram closely might have noticed that it was showing the transformer in the automatic version and how the relay breaks that circuit.

440
00:34:30,195 --> 00:34:35,117
I was so confused by the idea of the transformer not being in the furnace that it didn't even register what the diagram explained.

441
00:34:35,117 --> 00:34:38,242
Sometimes a multimeter brings a faster answer!